Basic Info.
Model NO.
Copper Conductor/XLPE Insulation/PVC Sheath
Application
Construction, Industrial, Power Station
Voltage
Low and Medium Voltage Cable
Wire Core Material
Bare Copper Wire
Model
Copper Conductor/XLPE Insulation/PVC Sheath
Rated Voltage
18/20kv,18/30kv
Shielding Layer
Copper Tape
Product Description
1,APPLICATION
YJV-Copper Conductor XLPE Insulated PVC Sheathed Power Cable
This product is suitable for using in power distribution networks or fixed installations for industrial equipments with rated voltage up to and including 26/35KV
2,BASIC INFORMATION
Code Name
YJV
Rated Voltage (Uo/U)
18/20KV,18/30KV
Cable Structure
Copper Conductor/XLPE Insulation/PVC Sheath
3,CONSTRUCTION
Conductor
Number of conductors:1,3
The conductors shall comply with the requirement given in IEC
Insulation
XLPE(Cross-linked Polyethylene) according to IEC
Sheath
PVC(Polyaluminium Chloride) according to IEC
Metal screen
Copper Tape Screen
4,CABLE STANDARDS
GB/T12706-2008,IEC,BS,ASTM and etc. upon request.
5,CHARACTERISTICS
Conductor temperature
Maximum conductor temperature in normal use: 90ºC
Max.short-circuit temperature
Maximum shall not exceed 250ºC(5s Max,Duration)
Installation temperature
Ambient temperature under installation shall not be below 0ºC
Minimum bending radius
The bending radius of cable: (D-Diameter of cable)
For Three Core Cable-------------------------------------≥15D
For Single Core Cable-------------------------------------≥20D
6,Voltage designation
The rated voltage of the cable for a given application shall be suitable for the operating conditions in the system in which the cable is used,and is expressed in the form of Uo/ U(Um)kV.
Where:
Uo-The rated power-frequency voltage between conductor and screen or metallic-sheath,for which the cable designed;
U-The rated power-frequency voltage between conductors, for which the cable designed:
Urn-The maximum value of the "hight system voltage " for which the equipment may he operated.
7,Rated voltaged of cable applied in three phrase system are given in table
U | Um | Uo |
First class | Second class |
1 | 1.2 | 0.6 | 0.6 |
3 | 3.6 | 1.8 | 3.6 |
6 | 7.2 | 3.6 | 6 |
10 | 12 | 6 | 8.7 |
15 | 17.5 | 8.7 | 12 |
20 | 24 | 12 | 18 |
35 | 42 | 21 | 26 |
Note:The first class cable suitable for one single-phrase earth-fault time does not exceed 1 min each time and Max. time not exceed 8 hours.and not exceed 125 hours in all in one year.
The second class cable suitable fir more earth-fault time and more better insulation performance.
8,Production Range of cable
Type | No. of cores | Nominal Cross sectional area m2 |
Copper conductor |
YJV | 1 | 25-630 |
3 | 25-630 |
*The armoured single-core cables are used for D.C system only. As for A.C system non-magnetic armoured material should be used. Or magnetic isolation measures should be applied. |
9,DIMENSIONS-YJV-18/20KV 18/30KV
Nominal cross sectional area of conductor(mm²) | Nominal insulation thickness(mm) | 18/20KV 18/30KV YJV |
Approx overall diameter(mm) | Cable weight max(kg/kn) |
1×35 | 8.0 | 31.9 | 1240 |
1×50 | 8.0 | 33.3 | 1560 |
1×70 | 8.0 | 34.9 | 1840 |
1×95 | 8.0 | 36.7 | 2140 |
1×120 | 8.0 | 38.2 | 2450 |
1×150 | 8.0 | 39.9 | 2790 |
1×185 | 8.0 | 41.5 | 3200 |
1×240 | 8.0 | 44.0 | 3800 |
1×300 | 8.0 | 46.3 | 4460 |
1×400 | 8.0 | 49.6 | 5530 |
1×500 | 8.0 | 52.8 | 6160 |
1x630 | 8.0 | 56.4 | 8020 |
3×50 | 8.0 | 68.4 | 5290 |
3×70 | 8.0 | 72.5 | 6240 |
3×95 | 8.0 | 75.9 | 7360 |
3×120 | 8.0 | 79.4 | 8350 |
3×150 | 8.0 | 82.6 | 9520 |
3×185 | 8.0 | 86.4 | 10830 |
3×240 | 8.0 | 91.4 | 12810 |
3×300 | 8.0 | 96.7 | 14920 |
3×400 | 8.0 | 103.8 | 18110 |
3x500 | 8.0 | 111.1 | 20990 |
3x630 | 8.0 | 119.2 | 25290 |
*Compacted conductor
Product Data Of Cable
Nominal cross-sectional area of conductor(mm²) | Max.D.C resistance of conductor at 20ºC(Ω/km) | Max.short circuit current of conductor at 90ºC |
Copper conductor | Copper conductor |
25 | 0.727 | 3.69 |
35 | 0.524 | 5.15 |
50 | 0.387 | 7.31 |
70 | 0.268 | 10.2 |
95 | 0.193 | 13.8 |
120 | 0.153 | 17.4 |
150 | 0.124 | 21.7 |
185 | 0.0991 | 26.7 |
240 | 0.0754 | 34.6 |
300 | 0.0601 | 43.1 |
400 | 0.0470 | 57.4 |
500 | 0.0366 | 71.7 |
630 | 0.0283 | 88.8 |
10,Voltage test and partial discharge test
No. | Test items | Rated Voltage KV |
18/20 18/30 |
1 | Power frency A.C.Voltage test (KV/5min) | 63 |
2 | Power frency A.C.Voltage test for 4 hours (KV) | 7 |
3 | Impluse voltage test(KV) | 170 |
4 | Partial discharge test maximum discharge at 1.73Uo pc | 5 |
The power-frequency voltage test of cables for rated voltage 21/35KV shall be done upon request according to 2.5Uo×30min or 3.5Uo×50min. |
11,Capacitance of cable(reference value)
Nominal cross-sectional area of conductor(mm²) | Rated Voltage KV |
18/20 18/30 |
Capacitance/phase μF/km |
25 | 0.1163 |
35 | 0.1251 |
50 | 0.1363 |
70 | 0.1508 |
95 | 0.1643 |
120 | 0.1760 |
150 | 0.1893 |
185 | 0.2026 |
240 | 0.2207 |
300 | 0.2387 |
400 | 0.2684 |
500 | 0.2876 |
630 | 0.3151 |
12,Inductance of cable
Nominal cross-sectional area of conductor(mm²) | Rated Voltage KV |
18/20 18/30 |
Capacitance/phase μF/km |
1x50 | 0.6501 |
1x70 | 0.6252 |
1x95 | 0.6043 |
1x120 | 0.5891 |
1x150 | 0.5740 |
1x185 | 0.5640 |
1x240 | 0.5487 |
1x300 | 0.5376 |
1x400 | 0.5219 |
1x500 | 0.5218 |
1x630 | 0.5012 |
3x50 | 0.4396 |
3x70 | 0.4145 |
3x95 | 0.3956 |
3x120 | 0.3799 |
3x150 | 0.3642 |
3x185 | 0.3485 |
3x240 | 0.3360 |
3x300 | 0.3266 |
3x400 | 0.3014 |
13,Short circuit current of mechanic-screen
Nominal cross-sectional area of conductor(mm²) | Rated Voltage KV |
18/20 18/30 |
Short circuit current |
1x50 | 1284 |
1x70 | 1281 |
1x95 | 1280 |
1x120 | 1279 |
1x150 | 1278 |
1x185 | 1275 |
1x240 | 1274 |
1x300 | 1271 |
1x400 | 1270 |
1x500 | 1266 |
1x630 | 1265 |
3x50 | 3031 |
3x70 | 3031 |
3x95 | 3031 |
3x120 | 3031 |
3x150 | 3031 |
3x185 | 3031 |
3x240 | 3031 |
3x300 | 3031 |
14,Current carrying capacity of cable
Copper conductor XLPE insulated power cable for rated voltage 18/30~26/35KV
Copper Conductor | Nominal Cross sectional area of conductor mm2 | In the air | In the ground |
Air temperature:40ºC | Air temperature:25ºC |
Single Core | Three Core | Single Core | Three Core |
| | | |
50 | 220 | 245 | 185 | 215 | 225 | 200 |
70 | 270 | 305 | 230 | 265 | 275 | 250 |
95 | 330 | 370 | 280 | 315 | 330 | 300 |
120 | 375 | 425 | 310 | 360 | 375 | 330 |
150 | 425 | 485 | 260 | 400 | 420 | 380 |
185 | 485 | 555 | 400 | 455 | 475 | 425 |
240 | 560 | 650 | 470 | 525 | 555 | 490 |
300 | 650 | 745 | 540 | 595 | 630 | 555 |
400 | 760 | 870 | 610 | 680 | 720 | 625 |
500 | 875 | 1000 | - | 775 | 825 | - |
630 | 1000 | 1160 | - | 875 | 940 | - |
Installation and Operation Condition of Cable
Max.Operation temperature of conductor-------------------------90ºC
Ambient air temperature----------------------------------------------- 40ºC.
Soil temperature----------------------------------------------------------25ºC.
Soil thermal resitivity---------------------------------------------------1.0ºCm/w
Buried depth---------------------------------------------------------------0.8m
Single-Circuit only
Single-core cable is installed in parallel.Adjacent space is equivalent to the diameter of the cable.
Correction factors of current carrying for different soil temperature
Soil temperature(ºC) | 15 | 20 | 25 | 30 | 35 | 40 | 45 |
Rating factor | 1.09 | 1.04 | 1.0 | 0.96 | 0.92 | 0.87 | 0.83 |
Correction factors of current carrying for different thermal temperature
Rating factors for soil Thermal resistivityºC.m/w | 1.0 | 1.2 | 1.5 | 2.0 | 2.5 | 3.0 | 3.5 |
Three cores | 1.0 | 0.943 | 0.877 | 0.792 | 0.736 | 0.675 | 0.641 |
Single core | 1.0 | 0.934 | 0.850 | 0.748 | 0.692 | 0.635 | 0.598 |
Correction factors of current carrying for different air temperature
Air temperature(ºC) | 20 | 25 | 30 | 35 | 40 | 45 | 50 |
Correction factor | 1.18 | 1.14 | 1.10 | 1.05 | 1.0 | 0.95 | 0.89 |
Address:
Room1116, Floor 11, Hongxing Jiuzhou International Plaza, Xincheng Road, Yixing, Wuxi, Jiangsu, China
Business Type:
Manufacturer/Factory, Trading Company
Business Range:
Chemicals, Electrical & Electronics, Service
Management System Certification:
ISO 9001, ISO 9000, ISO 14001, ISO 14000, ISO 20000, OHSAS/ OHSMS 18001
Company Introduction:
Established in 2014 and bringing together the factory more than 30 years of experience in cable, Lonheo is backed by the excellent reputation of our cooperated factory, All what we do is to make them as leading cable contractors in the world.
Lonheo is able to strive in today′s competitive business environment by creating synergy and consolidating the resources of all partners. This ensures that Lonheo remains operationally and financially strong.
With this strategic partnership in place, Lonheo is able to help our customers achieve their goals and provide greater value-added services to them.
Our company are focus on cable & wire supplyment and waste water treatment chemicals.
Our Features Product:
===Power Cables===
Ultra High Voltage, Power Cable, High Voltage Power Cable, Medium Voltage Power Cable, Low Voltage Power Cable, LSZH (low smoke zero halogen) Cable, XLPE Cable, AAAC (Aluminium Alloy Conductor) Power Cable, Armoured Cable, SWA (Steel Wire Armoured) Cable.
Power cables are mainly used for power transmission and distribution systems in the power industry and general industries.
===Wires and cables for electrical equipment===
Rubber Insulated Cable, Mining, Drilling & Tunnelling Cable, Ship Cable, Nylon Sheathed Wire, Plastic Insulated Control Cable.
Electrical Equipment Cables are mainly used to supply and distribute electricity.
===Aerial Cable===
Aerial Bundled Cable, Copper Stranded Wire, Aluminium Conductor Steel Reinforced (ACSR) Wires, Aluminium Alloy Conductors (AAAC), Aluminium Stranded Conductor (AAC).
These cables are mainly used as overhead power lines for power transmission and power distribution.
===Special Cables and Wires===
Fire Resistant Cable, High Temperature Resistant Cable, Rodent Resistant Cable / Termite Resistant Cable, Waterproof Cable, Eco-friendly Direct Current cable, Medium Voltage Power Cable for Subway and Light-weight, Wind Energy Cable, 1E Class Nuclear Cable, Energy Efficient ACSR, UHV Supporting and Expanding Overhead Wires, Flexible Fire-proof Cable for 0.6/1KV.