Basic Info.
Application
Industrial, Power Station
Voltage
High Voltage Cable
Material Shape
Round Wire
Wire Core Material
Bare Copper Wire
Model
Yjlw02,Yjlw02-Z,Yjlw03,Yjlw03-Z,Yjllw02,Yjllw02-Z
Name
Ehv Cable,High Voltage Cable,Hv Cables
Type of Conductor
Aluminium or Copper
Product Description
Construction Of Cable
CABLE STANDARDS
GB/T11017,GB/Z18890,GB/Z22078,IEC and etc. upon request.
Specification And Name
1. YJLW02
Power Cable with Copper Conductor, XLPE Insulation, Corrugated Aluminum Sheath, PVC Outer Sheath
2. YJLW02-Z
Longitudinal Water-blocking Power Cable with Copper conductor, XLPE Insulation, Corrugated Aluminum Sheath, PVC Outer Sheath
3. YJLW03
Power Cable with Copper Conductor, XLPE Insulation, Corrugated Aluminum Sheath, PE Outer Sheath
4. YJLW03-Z
Longitudinal Water-blocking Power Cable with Copper Conductor, XLPE Insulation, Corrugated Aluminum Sheath, PE Outer Sheath
5. YJLLW02
Power Cable with Aluminum Conductor, XLPE Insulation, Corrugated Aluminum Sheath, PVC Outer Sheath
6. YJLLW02-Z
Longitudinal Water-blocking Power Cable with Aluminum Conductor, XLPE Insulation, Corru-gated Aluminum Sheath, PVC Outer Sheath
7. YJLLW03
Power Cable with Aluminum Conductor, XLPE Insulation, Corrugated Aluminum Sheath, PE Outer Sheath
8. YJLLW03-Z
Longitudinal Water-blocking Power Cable with Aluminum Conductor. XLPE Insulation, Corrugated Aluminum Sheath, PE Outer Sheath
Operating Environment
1. Max admissible temperature for conductor:
90ºC under normal running condition; 250ºC under short circuit(max. duration is 5s)
2. Min bending radius is recommended to be 20 times of cable overall diameter
3. PVC sheathed cables shall not be installed if the environment temperature is below 0ºC,and if it is below 0ºC,the cable should be heated before the installation
Metal Sheath
1. Cables with corrugated aluminum sheath can be especially suitable for the following conditions in addition to the normal ones
2. Cables with corrugated aluminum sheath: places where there is not much corrosion but much requirement for mechanical strength (e.g. direct connection to transformers, laying on bridges and in vertical shafts)
Plastic Outer Sheath
1. Cables with PVC outer sheath ( Type 02 ) are suitable for high voltage transmission line with general fireproof requirement and centain insulation requirement for the outer sheath
2. Cables with PE outer sheath( Type 03 )are suitable for high voltage transmission line directly buried underground with higher insulation requirement on the outer sheath; and if they are laid in tunnels or vertical shafts, anti-fire and flame-retardant measures must be taken
XLPE Insulation Corrugated Aluminum Sheath For Rated Voltage Of 50/66kV
Conductor | Nominal thickness of insulation(mm) | Aluminium sheath thickness(mm) | Non-metallic thickness(mm) |
Norminal Cross-sectional Area(mm²) | Shape | Approx.diameter (mm) |
240 | Circular Compacted | 18.3 | 14.0 | 2.0 | 4.0 |
300 | 20.6 | 14.0 | 2.0 | 4.0 |
400 | 23.3 | 14.0 | 2.0 | 4.0 |
500 | 26.4 | 14.0 | 2.0 | 4.0 |
630 | 30.1 | 14.0 | 2.0 | 4.0 |
800 | Milliken conductor | 34.8 | 14.0 | 2.0 | 4.0 |
1000 | 38.8 | 14.0 | 2.3 | 4.0 |
1200 | 42.0 | 14.0 | 2.3 | 4.0 |
1400 | 45.2 | 14.0 | 2.3 | 4.0 |
1600 | 48.0 | 14.0 | 2.3 | 4.0 |
1800 | 50.8 | 14.0 | 2.3 | 4.0 |
2000 | 54.0 | 14.0 | 2.3 | 4.0 |
2200 | 57.4 | 14.0 | 2.3 | 4.0 |
2500 | 61.2 | 14.0 | 2.3 | 4.0 |
XLPE Insulation Corrugated Aluminum Sheath For Rated Voltage Of 50/66kV
Norminal Cross-sectional Area(mm²) | Approx. Overall diameter (mm) | Approx.weight of copper cable(kg/km) | Approx.weight of copper cable(kg/km) | Conductor D.C resistance at 20ºC (Ω/km) | Cable Capacity (μF/km) |
YJLW02 YJLW02-Z | YJLW03 YJLW03-Z | YJLLW02 YJLLW02-Z | YJLLW03 YJLLW03-Z | Copper conductor | Aluminium conductor |
240 | 78.0 | 6950 | 6460 | 5460 | 4970 | 0.0754 | 0.125 | 0.150 |
300 | 82.0 | 7670 | 7190 | 5810 | 5350 | 0.0601 | 0.100 | 0.162 |
400 | 83.0 | 8840 | 8320 | 6395 | 5880 | 0.0470 | 0.0778 | 0.174 |
500 | 86.0 | 10065 | 9510 | 7080 | 6420 | 0.0366 | 0.0605 | 0.189 |
630 | 91.0 | 11570 | 10990 | 7670 | 7090 | 0.0283 | 0.0469 | 0.207 |
800 | 97.0 | 14450 | 13740 | 9340 | 8788 | 0.0221 | 0.0367 | 0.228 |
1000 | 104.0 | 16730 | 16070 | 10290 | 9630 | 0.0176 | 0.0291 | 0.260 |
1200 | 107.0 | 18540 | 17870 | 10990 | 10320 | 0.0151 | 0.0247 | 0.268 |
1400 | 109.0 | 20570 | 19860 | 11900 | 11200 | 0.0129 | 0.0212 | 0.285 |
1600 | 114.0 | 22780 | 22070 | 12740 | 12000 | 0.0113 | 0.0186 | 0.298 |
1800 | 116.0 | 24690 | 23950 | 13560 | 12810 | 0.0101 | 0.0165 | 0.311 |
2000 | 120.0 | 26780 | 26030 | 14420 | 13650 | 0.0090 | 0.0149 | 0.326 |
2200 | 123.0 | 28920 | 28130 | 15300 | 14510 | 0.0083 | 0.0135 | 0.342 |
2500 | 126.0 | 31970 | 31160 | 16500 | 15680 | 0.0073 | 0.0127 | 0.359 |
XLPE Insulation Corrugated Aluminum Sheath For Rated Voltage Of 64/110kV
Conductor | Nominal thickness of insulation(mm) | Aluminium sheath thickness(mm) | Non-metallic thickness(mm) |
Norminal Cross-sectional Area(mm²) | Shape | Approx.diameter (mm) |
240 | Circular Compacted | 18.3 | 19.0 | 2.0 | 4.0 |
300 | 20.6 | 18.5 | 2.0 | 4.0 |
400 | 23.3 | 17.5 | 2.0 | 4.0 |
500 | 26.4 | 17.0 | 2.0 | 4.0 |
630 | 30.1 | 16.5 | 2.0 | 4.5 |
800 | Milliken conductor | 34.8 | 16.0 | 2.0 | 4.5 |
1000 | 38.8 | 16.0 | 2.3 | 4.5 |
1200 | 42.0 | 16.0 | 2.3 | 5.0 |
1400 | 45.2 | 16.0 | 2.3 | 5.0 |
1600 | 48.0 | 16.0 | 2.3 | 5.0 |
1800 | 50.8 | 16.0 | 2.3 | 5.0 |
2000 | 54.0 | 16.0 | 2.3 | 5.0 |
2200 | 57.4 | 16.0 | 2.3 | 5.0 |
2500 | 61.2 | 16.0 | 2.3 | 5.0 |
XLPE Insulation Corrugated Aluminum Sheath For Rated Voltage Of 64/110kV
Norminal Cross-sectional Area(mm²) | Approx. Overall diameter (mm) | Approx.weight of copper cable(kg/km) | Approx.weight of copper cable(kg/km) | Conductor D.C resistance at 20ºC (Ω/km) | Cable Capacity (μF/km) |
YJLW02 YJLW02-Z | YJLW03 YJLW03-Z | YJLLW02 YJLLW02-Z | YJLLW03 YJLLW03-Z | Copper conductor | Aluminium conductor |
240 | 88.0 | 8400 | 6530 | 6940 | 5070 | 0.0754 | 0.125 | 0.123 |
300 | 90.0 | 9040 | 7150 | 7210 | 5320 | 0.0601 | 0.100 | 0.134 |
400 | 91.0 | 9890 | 7980 | 7480 | 5570 | 0.0470 | 0.0778 | 0.149 |
500 | 93.0 | 10890 | 8910 | 7970 | 5990 | 0.0366 | 0.0605 | 0.164 |
630 | 97.0 | 12570 | 10270 | 8820 | 6520 | 0.0283 | 0.0469 | 0.183 |
800 | 104.0 | 15140 | 12660 | 9940 | 7470 | 0.0221 | 0.0367 | 0.215 |
1000 | 109.0 | 17740 | 15150 | 11220 | 8620 | 0.0176 | 0.0291 | 0.233 |
1200 | 114.0 | 19800 | 16840 | 12290 | 9330 | 0.0151 | 0.0247 | 0.241 |
1400 | 117.0 | 21910 | 20980 | 13240 | 12310 | 0.0129 | 0.0212 | 0.257 |
1600 | 120.0 | 24120 | 22875 | 14130 | 12970 | 0.0113 | 0.0186 | 0.266 |
1800 | 122.0 | 25480 | 24540 | 14320 | 13390 | 0.0101 | 0.0165 | 0.280 |
2000 | 126.0 | 27250 | 26310 | 14860 | 13930 | 0.0090 | 0.0149 | 0.293 |
2200 | 129.0 | 30400 | 29370 | 16780 | 15750 | 0.0083 | 0.0135 | 0.307 |
2500 | 133.0 | 33070 | 32040 | 17590 | 16570 | 0.0073 | 0.0127 | 0.322 |
XLPE Insulation Corrugated Aluminum Sheath For Rated Voltage Of 127/220kV
Conductor | Nominal thickness of insulation(mm) | Aluminium sheath thickness(mm) | Non-metallic thickness(mm) |
Norminal Cross-sectional Area(mm²) | Shape | Approx.diameter (mm) |
400 | Circular Compacted | 23.3 | 27.0 | 2.4 | 5.0 |
500 | 26.4 | 27.0 | 2.4 | 5.0 |
630 | 30.1 | 26.0 | 2.4 | 5.0 |
800 | Milliken conductor | 35.2 | 25.0 | 2.4 | 5.0 |
1000 | 39.5 | 24.0 | 2.6 | 5.0 |
1200 | 42.0 | 24.0 | 2.6 | 5.0 |
1400 | 45.2 | 24.0 | 2.6 | 5.0 |
1600 | 48.0 | 24.0 | 2.6 | 5.0 |
1800 | 50.8 | 24.0 | 2.8 | 5.0 |
2000 | 54.0 | 24.0 | 2.8 | 5.0 |
2200 | 57.4 | 24.0 | 2.8 | 5.0 |
2500 | 61.2 | 24.0 | 2.8 | 5.0 |
XLPE Insulation Corrugated Aluminum Sheath For Rated Voltage Of 64/110kV
Norminal Cross-sectional Area(mm²) | Approx. Overall diameter (mm) | Approx.weight of copper cable(kg/km) | Approx.weight of copper cable(kg/km) | Conductor D.C resistance at 20ºC (Ω/km) | Cable Capacity (μF/km) |
YJLW02 YJLW02-Z | YJLW03 YJLW03-Z | YJLLW02 YJLLW02-Z | YJLLW03 YJLLW03-Z | Copper conductor | Aluminium conductor |
400 | 118.0 | 12880 | 12090 | 10550 | 9760 | 0.0470 | 0.0778 | 0.144 |
500 | 121.0 | 14260 | 13450 | 11240 | 10430 | 0.0366 | 0.0605 | 0.122 |
630 | 123.0 | 15670 | 14850 | 11740 | 10920 | 0.0283 | 0.0469 | 0.135 |
800 | 129.0 | 17960 | 17100 | 12790 | 11920 | 0.0221 | 0.0367 | 0.154 |
1000 | 132.0 | 19920 | 19040 | 13730 | 12850 | 0.0176 | 0.0291 | 0.170 |
1200 | 135.0 | 22230 | 21320 | 14670 | 13760 | 0.0151 | 0.0247 | 0.180 |
1400 | 138.0 | 24290 | 23360 | 15620 | 14690 | 0.0129 | 0.0212 | 0.190 |
1600 | 141.0 | 26650 | 25690 | 16570 | 15910 | 0.0113 | 0.0186 | 0.198 |
1800 | 144.0 | 29710 | 28600 | 18570 | 17450 | 0.0101 | 0.0165 | 0.205 |
2000 | 146.0 | 30610 | 29620 | 18410 | 17430 | 0.0090 | 0.0149 | 0.213 |
2200 | 150.0 | 33270 | 31720 | 19660 | 18530 | 0.0083 | 0.0135 | 0.223 |
2500 | 157.0 | 35520 | 34460 | 20940 | 19870 | 0.0072 | 0.0127 | 0.234 |
Current-carrying capacity and import factors
Conductor cross-section Area | Voltage level |
66 KV | 110 KV | 220 KV |
Trefoil Laying | Parallel Laying | Trefoil Laying | Parallel Laying | Trefoil Laying | Parallel Laying |
In Air | Buried | In Air | Buried | In Air | Buried | In Air | Buried | In Air | Buried | In Air | Buried |
240 | 625 | 545 | 650 | 570 | 615 | 535 | 650 | 555 | - | - | - | - |
300 | 7 15 | 6 15 | 750 | 645 | 7 10 | 605 | 745 | 635 | - | - | - | - |
400 | 820 | 695 | 865 | 735 | 8 10 | 685 | 860 | 720 | 805 | 670 | 850 | 680 |
500 | 960 | 790 | 1010 | 835 | 936 | 780 | 1000 | 826 | 920 | 750 | 985 | 775 |
630 | 1090 | 890 | 1 170 | 950 | 1075 | 860 | 1 155 | 935 | 965 | 850 | 1 130 | 880 |
800 | 1330 | 1060 | 1435 | 1 120 | 1295 | 1035 | 1395 | 1090 | 1280 | 985 | 1385 | 1010 |
1000 | 1515 | 1 185 | 1640 | 1250 | 1470 | 1 150 | 1585 | 1225 | 1455 | 1080 | 1560 | 1 130 |
1200 | 1650 | 1275 | 1800 | 1360 | 1600 | 1235 | 1730 | 1320 | 1585 | 1 140 | 1710 | 1215 |
1400 | 1780 | 1360 | 1955 | 1460 | 1735 | 1325 | 1890 | 1415 | 1730 | 1205 | 1880 | 1290 |
1600 | 1930 | 1445 | 2 135 | 1560 | 1860 | 1405 | 2025 | 1505 | 1845 | 1260 | 2005 | l;150 |
1800 | 2050 | 1505 | 2260 | 1640 | 1965 | 1470 | 2 160 | 1575 | 1950 | 1290 | 2 130 | 1426 |
2000 | 2 160 | 1565 | 24 15 | 1725 | 2075 | 1635 | 2280 | 1655 | 2050 | 1310 | 2265 | 1450 |
2200 | 2260 | 1625 | 2560 | 1810 | 2180 | 1620 | 2415 | 1740 | 2 165 | 1350 | 2400 | 1500 |
2500 | 2380 | 1700 | 2720 | 1910 | 2320 | 1680 | 2580 | 1820 | 2305 | 1410 | 2530 | 1580 |
Current-carrying capacity and import factors
Conductor cross-section Area | Voltage level |
66 KV | 110 KV | 220 KV |
Trefoil Laying | Parallel Laying | Trefoil Laying | Parallel Laying | Trefoil Laying | Parallel Laying |
In Air | Buried | In Air | Buried | In Air | Buried | In Air | Buried | In Air | Buried | In Air | Buried |
240 | 485 | 425 | 510 | 445 | 460 | 420 | 505 | 435 | - | - | - | - |
300 | 555 | 480 | 585 | 505 | 550 | 475 | 580 | 496 | - | - | - | - |
400 | 650 | 550 | 680 | 575 | 640 | 540 | 660 | 570 | 625 | 530 | 645 | 550 |
500 | 750 | 625 | 795 | 660 | 740 | 620 | 790 | 650 | 730 | 605 | 775 | 625 |
630 | 875 | 715 | 925 | 755 | 860 | 705 | 920 | 745 | 835 | 690 | 905 | 735 |
800 | 1000 | 805 | 1065 | 850 | 985 | 795 | 1105 | 850 | 970 | 780 | 1090 | 835 |
1000 | 1130 | 895 | 1220 | 955 | 1115 | 885 | 1205 | 940 | 1100 | 870 | 1190 | 925 |
1200 | 1240 | 965 | 1340 | 1030 | 1215 | 955 | 1315 | 1015 | 1200 | 935 | 1305 | 1005 |
1400 | 1335 | 1025 | 1455 | 1105 | 1305 | 1015 | 1425 | 1085 | 1290 | 1005 | 1400 | 1065 |
1600 | 1420 | 1080 | 1555 | 1170 | 1390 | 1070 | 1520 | 1150 | 1370 | 1035 | 1505 | 1130 |
1800 | 1490 | 1120 | 1645 | 1220 | 1450 | 1110 | 1605 | 1190 | 1420 | 1090 | 1590 | 1180 |
2000 | 1565 | 1165 | 1745 | 1275 | 1530 | 1155 | 1695 | 1250 | 1500 | 1130 | 1665 | 1215 |
2200 | 1640 | 1210 | 1840 | 1330 | 1605 | 1200 | 1785 | 1330 | 1580 | 1175 | 1740 | 1235 |
2500 | 1750 | 1270 | 1970 | 1410 | 1710 | 1260 | 1910 | 1445 | 1695 | 1235 | 1840 | 1370 |
Assumed conditions for calculating Current-calculating Current: 1. Max. Operating temperature of conductor is 90ºC, and max. short circuit temperature of conductor is 250ºC; 2. single circuit,space between phases is cable diameter plus 70mm; 3. Ambient temperature is 35ºC; 4. Soil thermal resistance of direct butted is 1.0 k.m/W; depth of buried is 1000mm; 5. Earthing method: single point grounding or cross type bonding |
Direct buried ambient temperature is influence on current-carrying capacity |
Ambient temp | 10 | l6 | 20 | 26 | 30 | 35 | 40 | 45 |
Influence factor | 1.07 | 1.03 | 1.00 | 0.96 | 0.03 | 0.89 | 0.84 | 0.80 |
soil thermal resistance coefficient influence on current-carrying capacity |
Thermal resistance coefficient | 0.7 | 1 | 1 .2 | 1 .5 | 2 | 2.5 | 3 |
.Infinence fautor | 1.14 | 1.00 | 0.93 | 0.84 | 0.74 | 0.67 | 0.61 |
Direct buried depth is influence on current-carrying capacity |
Depth of direct buried | 500 | 700 | 900 | 1000 | 1200 | 1500 |
Influence factor | 1.10 | 1.05 | 1 .01 | 1.00 | 0.98 | 0.95 |
Air temperature's influence on current-carrying capacity |
Air temperature | 5 | l0 | l5 | 20 | 25 | 30 | 35 | 40 | 45 | 50 | 55 |
Influence factor | 1.24 | 1.21 | 1.16 | 1.13 | 1.08 | 1.04 | 1.00 | 0.96 | 0.90 | 0 .85 | 0.80 |
Single circuit parallel laying influence on current-carrying capacity |
Laying distance(mm) | D | D+70 | 200 | 250 | 300 | 350 | 400 | Note:D is cable's overall diameter |
Influence factor | 0.93 | 1.00 | 1.03 | 1.05 | 1.07 | 1.08 | 1.10 |
Short Circuit Current Unit:KA/1S
Conductor Cross-section area | Conductor Short circuit current |
Copper Conductor | Aluminium Conductor |
240 | 34.3 | 22.7 |
300 | 42.9 | 28.3 |
400 | 57.2 | 37.8 |
600 | 71.5 | 47.2 |
630 | 90.1 | 59.5 |
800 | 114.5 | 75.6 |
1000 | 143.0 | 94.5 |
1200 | 171.7 | 113.3 |
1400 | 200.3 | 132.2 |
1600 | 228.9 | 151.1 |
1800 | 257.5 | 170.0 |
2000 | 286.2 | 188.9 |
2200 | 314.8 | 207.8 |
2500 | 357.7 | 236.2 |
Process Flow Chart
Drawing Machine
Equipment Characteristics
1. Non-clip drawing machine with 13 dies and separate driving motors
2. Continuous annealing
3. Inert gases protection
4. Antioxidation material application
5. Continuously dual bobbins spooling
Frame-type Stranded RFS630-84
Technical Characteristics
1. Produce circular compacted conductor with cross sectional area up to and including It00 mm'
2. Produce the segment in milliken conductor with cross sectional area up to and including 3000mm²
3. Compacting coefficient comes to 0.89
4. Continuously automatic loading/unloading
5. With Max. Line speed of 60m/min
6. Intelligent control
Drum Twist Stranded DTPC3600
Technical Characteristics
1. Milliken conductor stranding into cironlarshape
2. Produce Milliken conductor with cross-sectional area up to atincluding 3000hnm²
3. Taping with constant tension
VCV Production Line
Equipment Characteristics
1. Maillefer water cooling extruder unit is most suitable for extrusion of high voltage XLPE.
2. Central Water Station Temperature Control:no noise,being easy to control temperature and pressure,being equipped with precise proportional valve to ensure stable,temperature control and having no effect on generator room's constant temperature(extremely critical for high-pressure production).
3. The best crosshead focusing on production of high voltage cables or extra high viltage cables is Maillefer's flat crosshead, which is characterized with fast and stable flow rate,eliminating the entangling risk .Tue to its long flows,there is no temperature interference between inner and outer shield layers and insulation layer.
4. Energy efficient direct tube heating system.
5. Maillefer is the first company who proposed the concept of post-heating and using the most stable pre-heating machine called YIFUDE in the world.
Degas
Equipment Characteristics
1. Regular gas-exchange
2. Intelligent temperature control
Technical characteristics
1. expertise, its function is to eliminate the residual gas of VCV production process.
2. eliminate the insulation thermal stress insulation heating stress further.
Metallic Sheath Production Line
Equipment Characteristics
1. Welding with double torch, and neat screen
2. Welding various materials such as copper,aiummum and stainless steel
3. Metallic sheath diameter is up to and including 200mm²
4. Online inspection for the welding scam flaw
Technical characteristics
1. With continues wave, free adjustment of the depth and pitch
2. Even thickness of the metal sheath,without any eccentricity,sand hole,blister and transverse crack
3. Outstanding water blocking performance
4. Meeting short-circuit current capacity
Outer Sheath Production Line
Equipment Characteristics
1. Two extruders with diameter of 911 and 1511 running together can realize the extrusion of single layer or double layers with different materials simultaneously
2. With graphite coating equipment
3. Measuring device for the overall diameter
4. Jetting, printing and meter counting equipment
5. Max. Diameter for the pay-off drum and take-up drum is 4200mm
Equipment Advantage
1. Produce outer sheath with cable overall diameter up to and including 200mm
2. Excellent control for outer diameter and eccentricity
Test System
Equipment Characteristics
1. All-metal shielding mom with dimension of 35m x 30m x 20m
2. Series resonant system with max. voltage of 700kV, 35A
3. Tests for resistance, capacitance, and dielectric loss, partial discharge and withstand voltage
4. Max. Load capacitance of 637μf
Package
1. Pack according to national standard or customer' s require-ment;
2. Professional package design, firm and durable,protect the cable effectively
Address:
Room1116, Floor 11, Hongxing Jiuzhou International Plaza, Xincheng Road, Yixing, Wuxi, Jiangsu, China
Business Type:
Manufacturer/Factory, Trading Company
Business Range:
Chemicals, Electrical & Electronics, Service
Management System Certification:
ISO 9001, ISO 9000, ISO 14001, ISO 14000, ISO 20000, OHSAS/ OHSMS 18001
Company Introduction:
Established in 2014 and bringing together the factory more than 30 years of experience in cable, Lonheo is backed by the excellent reputation of our cooperated factory, All what we do is to make them as leading cable contractors in the world.
Lonheo is able to strive in today′s competitive business environment by creating synergy and consolidating the resources of all partners. This ensures that Lonheo remains operationally and financially strong.
With this strategic partnership in place, Lonheo is able to help our customers achieve their goals and provide greater value-added services to them.
Our company are focus on cable & wire supplyment and waste water treatment chemicals.
Our Features Product:
===Power Cables===
Ultra High Voltage, Power Cable, High Voltage Power Cable, Medium Voltage Power Cable, Low Voltage Power Cable, LSZH (low smoke zero halogen) Cable, XLPE Cable, AAAC (Aluminium Alloy Conductor) Power Cable, Armoured Cable, SWA (Steel Wire Armoured) Cable.
Power cables are mainly used for power transmission and distribution systems in the power industry and general industries.
===Wires and cables for electrical equipment===
Rubber Insulated Cable, Mining, Drilling & Tunnelling Cable, Ship Cable, Nylon Sheathed Wire, Plastic Insulated Control Cable.
Electrical Equipment Cables are mainly used to supply and distribute electricity.
===Aerial Cable===
Aerial Bundled Cable, Copper Stranded Wire, Aluminium Conductor Steel Reinforced (ACSR) Wires, Aluminium Alloy Conductors (AAAC), Aluminium Stranded Conductor (AAC).
These cables are mainly used as overhead power lines for power transmission and power distribution.
===Special Cables and Wires===
Fire Resistant Cable, High Temperature Resistant Cable, Rodent Resistant Cable / Termite Resistant Cable, Waterproof Cable, Eco-friendly Direct Current cable, Medium Voltage Power Cable for Subway and Light-weight, Wind Energy Cable, 1E Class Nuclear Cable, Energy Efficient ACSR, UHV Supporting and Expanding Overhead Wires, Flexible Fire-proof Cable for 0.6/1KV.