Basic Info.
Application
Construction, Industrial, Power Station
Material Shape
Round Wire
Wire Core Material
Bare Copper Wire
Certification
ISO, CCC, VDE, TUV
Transport Package
Steel Drum, Wooden Drum, Steel Wooden Drum
Product Description
1,APPLICATION
YJV32-Copper Conductor XLPE Insulated Steel Wire Armoured PVC Sheathed Power Cable
This product is suitable for using in power distribution networks or fixed installations for industrial equipments with rated voltage up to and including 0.6/1KV
2,BASIC INFORMATION
Code Name
YJV32
Rated Voltage (Uo/U)
0.6/1KV
Cable Structure
Copper Conductor/XLPE Insulation/Steel Wire Aroured /PVC Sheath
3,CONSTRUCTION
Conductor
Number of conductors:1,2,3,4,5,3+1,4+1
The conductors shall comply with the requirement given in IEC
Insulation
XLPE(Cross-linked Polyethylene) according to IEC
Sheath
PVC(Polyaluminium Chloride) according to IEC
Armoured
Steel Wire
4,CABLE STANDARDS
GB/T12706-2008,IEC,BS,ASTM and etc. upon request.
5,CHARACTERISTICS
Conductor temperature
Maximum conductor temperature in normal use: 90ºC
Max.short-circuit temperature
Maximum shall not exceed 250ºC(5s Max,Duration)
Installation temperature
Ambient temperature under installation shall not be below 0ºC
Minimum bending radius
The bending radius of cable: (D-Diameter of cable)
-------------------------------------≥15D
6,Voltage designation
The rated voltage of the cable for a given application shall be suitable for the operating conditions in the system in which the cable is used,and is expressed in the form of Uo/ U(Um)kV.
Where:
Uo-The rated power-frequency voltage between conductor and screen or metallic-sheath,for which the cable designed;
U-The rated power-frequency voltage between conductors, for which the cable designed:
Urn-The maximum value of the "hight system voltage " for which the equipment may he operated.
7,Rated voltaged of cable applied in three phrase system are given in table
U
Um
Uo
First class
Second class
1
1.2
0.6
0.6
3
3.6
1.8
3.6
6
7.2
3.6
6
10
12
6
8.7
15
17.5
8.7
12
20
24
12
18
35
42
21
26
Note:The first class cable suitable for one single-phrase earth-fault time does not exceed 1 min each time and Max. time not exceed 8 hours.and not exceed 125 hours in all in one year.
The second class cable suitable fir more earth-fault time and more better insulation performance.
8,Production Range of cable
Type
No. of cores
Nominal Cross sectional area m2
Copper conductor
YJV32
2
10-400
3
10-630
4
10-500
3+1
10-630
5
10-500
4+1
10-500
3+2
10-500
*The armoured single-core cables are used for D.C system only. As for A.C system non-magnetic armoured material should be used. Or magnetic isolation measures should be applied.
9,DIMENSIONS-YJV32 -Table 01
Nominal cross sectional area of conductor(mm²)
Nominal insulation thickness(mm)
0.6/1KV YJV32
Approx overall diameter(mm)
Cable weight max(kg/km)
Circular
Sector
2×10
0.7
20.0
-
912
2×16
0.7
22.0
-
920
2×25
0.9
25.6
-
1156
2×35
0.9
27.8
-
1328
2×50*
1.0
30.0
26.4
1231
2×70*
1.1
35.2
30.0
1733
2×95*
1.1
39.0
34.0
2022
2×120*
1.2
42.4
35.4
2328
2×150*
1.4
47.2
40.6
3799
2×185*
1.6
52.2
44.4
4305
2×240*
1.7
57.8
-
5124
2×300*
1.8
63.5
-
6408
* Compacted conductor
DIMENSIONS-YJV32 -Table 02
Nominal cross sectional area of conductor(mm²)
Nominal insulation thickness(mm)
0.6/1KV YJV32
Approx overall diameter(mm)
Cable weight max(kg/km)
Circular
Sector
3×10
0.7
20.8
-
1049
3×16
0.7
23.0
-
1323
3×25
0.9
26.9
-
1779
3×35
0.9
29.5
-
2174
3×50*
1.0
31.8
28.6
2433
3×70*
1.1
37.6
32.8
3429
3×95*
1.1
41.8
37.0
4327
3×120*
1.2
46.7
40.6
5567
3×150*
1.4
51.4
45.1
7269
3×185*
1.6
56.1
49.6
8466
3×240*
1.7
62.1
54.2
10508
3×300*
1.8
67.9
59.2
12831
3×400*
2.0
76.5
66.0
17033
* Compacted conductor
DIMENSIONS-YJV32 -Table 03
Nominal cross sectional area of conductor(mm²)
Nominal insulation thickness(mm)
0.6/1KV YJV32
Approx overall diameter(mm)
Cable weight max(kg/km)
Circular
Sector
4×10
0.7
22.2
-
1217
4×16
0.7
24.6
-
1560
4×25
0.9
29.0
-
2132
4×35
0.9
31.9
-
2649
4×50*
1.0
35.5
34.4
3218
4×70*
1.1
40.9
38.8
4312
4×95*
1.1
46.8
45.5
5468
4×120*
1.2
57.5
48.6
7479
4×150*
1.4
56.0
52.4
9090
4×185*
1.6
61.9
59.6
10587
4×240*
1.7
68.1
65.7
13238
4×300*
1.8
75.9
72.1
16273
4×400*
2.0
84.4
80.2
21519
*Compacted conductor
DIMENSIONS-YJV32 -Table 04
Nominal cross sectional area of conductor(mm²)
Nominal insulation thickness(mm)
0.6/1KV YJV32
Approx overall diameter(mm)
Cable weight max(kg/km)
Circular
Tile Shape
5×10
0.7
23.7
-
1391
5×16
0.7
26.4
-
1805
5×25
0.9
31.5
-
2510
5×35
0.9
35.4
-
3375
5×50*
1.0
39.5
-
4093
5×70*
1.1
45.1
42.6
5326
5×95*
1.1
51.3
48.8
7432
5×120*
1.2
56.0
52.4
8999
5×150*
1.4
61.6
57.8
10936
5×185*
1.6
67.7
63.0
12793
5×240*
1.7
75.9
71.1
16041
5×300*
1.8
83.6
77.9
20754
5×400*
2.0
92.6
-
26123
*Compacted conductor
DIMENSIONS-YJV32 -Table 05
Nominal cross sectional area of conductor(mm²)
No.of cores
Nominal insulation thickness(mm)
0.6/1KV YJV32
Approx overall diameter(mm)
Cable weight max(kg/km)
Circular
Sector
3x10+1x6
3
0.7
21.5
-
1137
1
0.7
3x16+1x10
3
0.7
24.0
-
1471
1
0.7
3x25+1x16
3
0.9
27.9
-
1984
1
0.7
3x35+1x16
3
0.9
30.1
-
2372
1
0.7
3x50+1x25
3*
1.0
34.0
35.2
2807
1
0.9
3x70+1x35
3*
1.1
39.1
39.8
4012
1
0.9
3x95+1x50
3*
1.1
43.4
45.3
5038
1
1.0
3x120+1x70
3*
1.2
48.9
49.0
6809
1
1.1
3x150+1x70
3*
1.4
52.8
53.2
7991
1
1.1
3x185+1x95
3*
1.6
58.0
60.0
9444
1
1.1
3x240+1x120
3*
1.7
64.1
66.5
11722
1
1.2
3x300+1x150
3*
1.8
69.9
71.4
14392
1
1.4
3x400+1x185
3*
2.0
79.3
81.0
18892
1
1.6
*Compacted conductor
DIMENSIONS-YJV32 -Table 06
Nominal cross sectional area of conductor(mm²)
No.of cores
Nominal insulation thickness(mm)
0.6/1KV YJV32
Approx overall diameter(mm)
Cable weight max(kg/km)
Circular
Tile Shape
4x10+1x6
4
0.7
23.1
-
1317
1
0.7
4x16+1x10
4
0.7
25.9
-
1722
1
0.7
4x25+1x16
4
0.9
30.5
-
2370
1
0.7
4x35+1x16
4
0.9
33.1
-
2858
1
0.7
4x50+1x25
4*
1.0
38.3
-
3815
1
0.9
4x70+1x35
4*
1.1
43.5
40.8
4920
1
0.9
4x95+1x50
4*
1.1
48.9
46.8
6858
1
1.0
4x120+1x70
4*
1.2
54.1
50.8
8318
1
1.1
4x150+1x70
4*
1.4
58.2
55.0
9867
1
1.1
4x185+1x95
4*
1.6
64.5
60.6
11681
1
1.1
4x240+1x120
4*
1.7
71.0
66.6
14589
1
1.2
4x300+1x150
4*
1.8
79.5
74.3
18951
1
1.4
4x400+1x185
4*
2.0
87.9
-
23553
1
1.6
*Compacted conductor
DIMENSIONS-YJV32 -Table 07
Nominal cross sectional area of conductor(mm²)
No.of cores
Nominal insulation thickness(mm)
0.6/1KV YJV32
Approx overall diameter(mm)
Cable weight max(kg/km)
Circular
Tile Shape
3x10+2x10
3
0.7
22.5
-
1244
2
0.7
3x16+2x10
3
0.7
25.3
-
1639
2
0.7
3x25+2x16
3
0.9
29.5
-
2217
2
0.7
3x35+2x16
3
0.9
31.3
-
2596
2
0.7
3x50+2x25
3*
1.0
36.7
-
3494
2
0.9
3x70+2x35
3*
1.1
41.7
40.6
4497
2
0.9
3x95+2x50
3*
1.1
46.8
46.6
6265
2
1.0
3x120+2x70
3*
1.2
52.3
50.8
7674
2
1.1
3x150+2x70
3*
1.4
55.4
54.8
8866
2
1.1
3x185+2x95
3*
1.6
61.4
60.4
10615
2
1.1
3x240+2x120
3*
1.7
67.4
66.4
13161
2
1.2
3x300+2x150
3*
1.8
75.1
73.7
16178
2
1.4
3x400+2x185
3*
2.0
83.4
-
21091
2
1.6
*Compacted conductor
DIMENSIONS-YJV32 -Table 08
Product Data Of Cable
Nominal cross-sectional area of conductor(mm²)
Max.D.C resistance of conductor at 20ºC(Ω/km)
Copper
1
18.1
1.5
12.1
2.5
7.41
4
4.61
6
3.08
10
1.83
16
1.15
25
0.727
35
0.524
50
0.387
70
0.268
95
0.193
120
0.153
150
0.124
185
0.0991
240
0.0754
300
0.0601
400
0.0470
500
0.0366
630
0.0283
800
0.0021
Power frequency A.C. Voltage test
Test voltage 3.5kV/5 min
10,Current carrying capacity of cable
l In the air
Conductor
Nominal Cross sectional area of conductor mm2
Armoured cable
Single Core
Two Core
Three cores
&
Five cores
Copper Conductor
1.5
21
24
-
-
2.5
31
41
-
-
4
41
54
-
-
6
52
68
-
-
10
71
93
75
64
16
92
120
97
83
25
120
155
125
110
35
150
195
155
135
50
180
235
190
165
70
230
295
245
210
95
285
370
300
260
120
335
430
355
305
150
385
495
400
345
185
450
570
460
395
240
535
680
-
465
300
620
790
-
535
400
720
920
-
620
500
835
1080
-
-
630
960
1260
-
-
800
1110
1470
-
-
11,Current carrying capacity of cable
l In the ground
Conductor
Nominal Cross sectional area of conductor mm2
Armoured cable
Single Core
Two Core
Three cores
&
Five cores
Copper Conductor
1.5
25
28
-
-
2.5
42
46
45
35
4
55
59
59
50
6
69
74
74
60
10
92
98
100
85
16
115
125
135
110
25
150
160
165
140
35
180
190
200
170
50
215
230
240
200
70
265
280
295
245
95
320
335
355
300
120
360
385
405
335
150
410
430
455
380
185
460
490
515
430
240
535
570
-
500
300
605
645
-
565
400
685
735
-
650
500
775
840
-
-
630
865
950
-
-
800
960
1080
-
-
12,Installation and Operation Condition of Cable
l
In the air
1.The distance between two adjacent cable' axle centers of single-core cables laid in parallel cross-section area of conductor≤185mm²;2 times of the cable diameter cross-sectional area of conductor≥240mm²;90mm
2.Ambient air temperature:30ºC.
3.Max.continous operating temperature of conductor: 90ºC.
l
Current carrying rating factors for different ambient air temperature
Ambient air temperature
20ºC
25ºC
30ºC
35ºC
40ºC
45ºC
Correction factor
1.09
1.04
1.00
0.95
0.90
0.84
l
Directly in the ground
1.The single-core cables are installed separately.The distance between the cable
center is 2 times of the cable Diameter.
2.Soil temperature: 25ºC.
3.Max.continous operating temperature of
conductor: 90ºC.
4.Thermal resistivity of soil : 1.0 ºC. m/W
5.Depth of Direct-Buried:0.7m.
l
Current carrying rating factors for different soil temperature
Soil temperature
20ºC
25ºC
30ºC
35ºC
40ºC
Correction factor
1.04
1.0
0.96
0.92
0.87
Address:
Room1116, Floor 11, Hongxing Jiuzhou International Plaza, Xincheng Road, Yixing, Wuxi, Jiangsu, China
Business Type:
Manufacturer/Factory, Trading Company
Business Range:
Chemicals, Electrical & Electronics, Service
Management System Certification:
ISO 9001, ISO 9000, ISO 14001, ISO 14000, ISO 20000, OHSAS/ OHSMS 18001
Company Introduction:
Established in 2014 and bringing together the factory more than 30 years of experience in cable, Lonheo is backed by the excellent reputation of our cooperated factory, All what we do is to make them as leading cable contractors in the world.
Lonheo is able to strive in today′s competitive business environment by creating synergy and consolidating the resources of all partners. This ensures that Lonheo remains operationally and financially strong.
With this strategic partnership in place, Lonheo is able to help our customers achieve their goals and provide greater value-added services to them.
Our company are focus on cable & wire supplyment and waste water treatment chemicals.
Our Features Product:
===Power Cables===
Ultra High Voltage, Power Cable, High Voltage Power Cable, Medium Voltage Power Cable, Low Voltage Power Cable, LSZH (low smoke zero halogen) Cable, XLPE Cable, AAAC (Aluminium Alloy Conductor) Power Cable, Armoured Cable, SWA (Steel Wire Armoured) Cable.
Power cables are mainly used for power transmission and distribution systems in the power industry and general industries.
===Wires and cables for electrical equipment===
Rubber Insulated Cable, Mining, Drilling & Tunnelling Cable, Ship Cable, Nylon Sheathed Wire, Plastic Insulated Control Cable.
Electrical Equipment Cables are mainly used to supply and distribute electricity.
===Aerial Cable===
Aerial Bundled Cable, Copper Stranded Wire, Aluminium Conductor Steel Reinforced (ACSR) Wires, Aluminium Alloy Conductors (AAAC), Aluminium Stranded Conductor (AAC).
These cables are mainly used as overhead power lines for power transmission and power distribution.
===Special Cables and Wires===
Fire Resistant Cable, High Temperature Resistant Cable, Rodent Resistant Cable / Termite Resistant Cable, Waterproof Cable, Eco-friendly Direct Current cable, Medium Voltage Power Cable for Subway and Light-weight, Wind Energy Cable, 1E Class Nuclear Cable, Energy Efficient ACSR, UHV Supporting and Expanding Overhead Wires, Flexible Fire-proof Cable for 0.6/1KV.